Select:      
  Features
  Download Demo Software
  Download PDF brochure
  Relay, Meter Testing, GPS, ATD & CT Mag Curve Interfaces
  Hire this test set
(UK only)

APTS3 - Automatic Protection Test Set


 

  • Digital Signal Processing based technology

  • 2000VA total high power / high burden outputs

  • Advanced low-noise high-frequency switching amplifier technology throughout

  • Effortlessly tests the highest burden electromechanical relays

  • 3x individually isolated 300V voltage sources (1x 900V by series connection)

  • 3x individually isolated 35A current sources (1x 105A by parallel connection)

  • Integrated 0-260Vdc battery simulator and dual-channel storage oscilloscope

Now in its third generation, the APTS three-phase protection relay test set is the flagship multipurpose relay test set manufactured by RES. The APTS utilises the latest digital signal processing based waveform synthesis techniques coupled with advanced low-noise switching amplifier technology. This combination enables the APTS to deliver precision waveforms at the highest output power available in a portable lightweight computerised test set anywhere. The highest burden single & three-phase electromechanical relays as well as the latest microprocessor based relays can be tested directly and without the need for additional accessories or amplifiers.

Interfaces for CT testing, Meter Testing, Transformer Differential protection relay testing and GPS clock syncronisation are also available as is a range of special purpose relay hardware interfaces.

 

Features - Software (see brochure for more info)

The supplied WindowsTM based software package fully controls the test set from any suitable laptop computer. This comprehensive package offers automatic testing modes for a large number of relay types as well as advanced manual testing facilities.

  • Windows 98/NT/2000/XP
  • All features and relay types supplied as standard
  • Fully Automatic or Manual Control
  • Extensive results archiving, presentation and printing features as well as error/trend analysis
  • Full on-line operating manual
  • COMTRADE/DFR/EMTP replay
  • Results are fully traceable to test set hardware, software and calibration data.


Features - Hardware
(see brochure for full detailed specs)

Voltage Outputs

  • Three fully independent & floating outputs 
  • 0-300Vac Range / 300VA Power
    <0.15% Error Typ., 0.25% Max.
    0.01V Resolution, <0.15% Distortion
  • Single 0-900Vac o/p via series connection

Current Outputs (3-Ph Mode)

  • Three fully independent & floating outputs 
  • 0-35A Range / 300VA Power
    ±90V peak (63Vrms) Compliance Voltage
    <0.15% Error Typ., 0.25% Max.
    0.001A Resolution, <0.15% Distortion

Current Output (1-Ph Parallel Mode)

  • 0-105A Range / 900VA Power
    ±90V peak (63Vrms) Compliance Voltage
    <0.3% Error Typ., 0.5% Max.
    0.001A Resolution, <0.3% Distortion

Current Outputs (3-Phase Series Mode)

  • 0-5A Range / 900VA Power
    ±270V peak (191Vrms) Compliance Voltage
    <0.3% Error Typ., 0.5% Max.
    0.001A Resolution, <0.3% Distortion

Frequency

  • DC to 4 kHz System bandwidth
    0.001 Hz Freq Resolution
    < ±10 ppm (< ± 0.001%) Error
  • Mains Sync Feature: precise PLL freq & phase lock to input supply freq. (40-70Hz)

Phase Angle

  • 0-360º Range
  • 0.01º Resolution
  • < ±0.1º Error

Contact Inputs

  • 6x contact inputs, individually isolated
  • Software selectable as wet/dry, contact/2.5-300V AC/DC voltage
  • 10kHz sample rate (±0.1msec resolution)

Contact Outputs

  • 6x contact outputs, individually isolated
  • Rated 10A@300Vac or 1A@150Vdc
  • 10kHz update rate (±0.1msec resolution)

Timer

  • 0-99999.9999 sec Range
    < 10 ppm (0.001%) Error, ±0.1msec Resolution
  • Synchronised to waveform generation

DC Supply Output

  • 0-260Vdc, 200W Power
    <0.5% Error, Ripple <0.2% of range
    0.01V Resolution
  • High startup-surge capability

Scope Input

  • Two isolated input channels 
  • ±10V, ±100V & ±500V ranges, 12-bit resolution, < 0.5% Error
  • Synchronised to waveform generation
  • Simultaneous recording of contact inputs
  • Large acquisition memory permits recording time of up to 3.5sec at 10kHz.

 Miscellaneous

  • Interface for comms to PC parallel port
  • RS232 interface for relay comms
  • Expansion Interface connector
  • Software based calibration
  • Comprehensive Overload, Thermal and Externally applied voltage protection on outputs
Input Power
  • Fully automatic universal input: 90-260V 45-65Hz AC
  • 200W no load, 2400W continuous max
  • Active Electronic Power Factor Correction (CosΦ>0.99)
Physical/Environmental
  • 0-50°C Operating Temperature
  • 5-95% Relative humidity (non-condensing)
  • IP20 Protected Enclosure
  • CE Marked, Tested to EN50081-2 (emissions) & EN50082-2 (susceptibility)
  • 380x210x400mm (not including handle)
  • 17.5kg Weight

Download APTS demo program

Download the full brochure - APTS3brochure.PDF (1.2Mb)


Download FREE PDF reader

 

   

Questions? Please email info@relayeng.com

©2003 Relay Engineering Services Ltd.
All rights reserved.